GENERAL INFORMATION
|
 |
 |
|
Model Name |
SLP-1500AP |
 |
|
AC INPUT
|
 |
|
AC Input
Capacity on Battery |
1500VA |
 |
|
AC Input
Voltage |
100V
or 110V/120V (+/-) 25%
at line input |
 |
|
AC Input
Frequency |
50 or 60
Hz+/-10% (auto sensing) |
 |
|
AC OUTPUT
|
 |
|
AC Output
Voltage |
Simulated
sine ware at 100V or
110V/115V/120V or 220V/230V/240V
+/-5% |
 |
|
AC Output
Frequency |
50 or 60
Hz +/- 0.5% |
 |
|
AC Output
Voltage Regulation |
AVR
automatically increase output
voltage 15% above input voltage
if -9% to -25% of nominal. AVR
decrease output voltage 13%
below input voltage if +9% to
+25% of nominal |
 |
|
AC Output
Transfer |
2/4
milliseconds, including
detection time |
 |
|
PROTECTION
|
 |
|
Protection
Spike |
320
Joules, 2ms |
 |
|
Protection
EMI/RFI |
10dB at
0.15 MHz, 50 dB at 30 MHz |
 |
|
Protection
Overload |
UPS
automatic shutdown if overload
exceeds 110% nominal at 60 sec
and 130% at 3 sec |
 |
|
Protection
Unit |
Fuse for
overload & short circuit
protection |
 |
|
Protection
10 BaseT |
Network (UTP,
RJ-45) compatible jacks |
 |
|
Protection
Short Protection |
UPS output
cut off immediately or input
fuse protection |
 |
|
BATTERY
|
 |
|
Battery
Type |
Sealed,
Maintenance-free lead acid, with
3 - 6 years typical lifetime |
 |
|
Battery
Typical |
4 hours
(to 90% of full capacity) |
 |
|
Battery
Protection |
Automatic
self-test & discharge
protection, replace battery
indicator |
 |
|
Battery
Run Time |
70 - 80
minutes |
 |
|
PHYSICAL
|
 |
|
Physical
Weight kgs Tower |
15.6 |
 |
|
Physical
Weight lbs Tower |
(34.3lb) |
 |
|
Physical
Dimension mm Tower |
130x382x201 |
 |
|
Physical
Dimension of Tower in inches |
(5.1x15x7.9) |
 |
|
INDICATOR
|
 |
|
LED |
LED |
 |
|
ALARM
|
 |
|
Alarm
Battery Backup |
Slow
beeping sound (about 0.47 Hz) |
 |
|
Alarm
Battery Low |
Rapid
beeping sound (about 1.82Hz) |
 |
|
Alarm
Overload |
Continue
beeping sound |
 |
|
INTERFACE
|
 |
|
Interface
RS-232 |
Bi-directional communication
port |
 |
|
ENVIRONMENT
|
 |
|
Environment Ambient |
3,500
meters max. elevation, 0-95%
humidity non-condensing, 0-40
deg c |
 |
|
Environment Audible |
<40dBA (1
meter from surface) |
|