SLP-3000P

 
 
GENERAL INFORMATION
 
   
Model Name SLP-3000P

 

AC INPUT
 
AC Input Capacity on Battery 3000VA
Input Connector NEMA L5-30P
AC Input Voltage (+/-) 25% at line input
AC Input Frequency 50 or 60 Hz+/-10% (auto sensing)

 

AC OUTPUT
 
AC Output Voltage Simulated sine ware at 100V or 110V/115V/120V or 220V/230V/240V +/-5%
AC Output Frequency 50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal
AC Output Transfer 2/4 milliseconds, including detection time

 

PROTECTION
 
Protection Spike 320 Joules, 2ms
Protection EMI/RFI 10dB at 0.15 MHz, 50 dB at 30 MHz
Protection Overload UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec
Protection Unit Fuse for overload & short circuit protection
Protection 10 BaseT Network (UTP, RJ-45) compatible jacks
Protection Short Protection UPS output cut off immediately or input fuse protection

 

BATTERY
 
Battery Type Sealed, Maintenance-free lead acid, with 3 - 6 years typical lifetime
Battery Typical 4 hours (to 90% of full capacity)
Battery Protection Automatic self-test & discharge protection, replace battery indicator
Battery Run Time 140 - 160 minutes

 

PHYSICAL
 
Physical Weight kgs Tower 20.5
Physical Weight lbs Tower (45.1lb)
Physical Dimension mm Tower 298x685x360
Physical Dimension inch Tower (11.7

 

INDICATOR
 
LED LED

 

ALARM
 
Alarm Battery Backup Slow beeping sound (about 0.47 Hz)
Alarm Battery Low Rapid beeping sound (about 1.82Hz)
Alarm Overload Continue beeping sound

 

INTERFACE
 
Interface RS-232 Bi-directional communication port

 

ENVIRONMENT
 
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c
Environment Audible <40dBA (1 meter from surface)