GENERAL
INFORMATION
|
 |
|
Model
Name |
SLR-1000P |
 |
 |
|
AC
INPUT
|
 |
| AC
Input Capacity on Battery |
1000VA |
 |
| AC
Input Voltage |
120v
(+/-) 25% at line input |
 |
| AC
Input Frequency |
50/60 Hz+/-10% (auto sensing) |
 |
|
AC
OUTPUT
|
 |
| AC
Output Voltage |
Simulated sine ware at
100V/110V/115V/120V/220V/230V/240V +/-5% |
 |
| AC
Output Frequency |
50 or 60 Hz +/- 0.5% |
 |
| AC
Output Voltage Regulation |
AVR automatically increase output
voltage 15% above input voltage if -9% to -25% of nominal.
AVR decrease output voltage 13% below input voltage if +9%
to +25% of nominal |
 |
| AC
Output Transfer |
2/4 milliseconds, including detection
time |
 |
|
PROTECTION
|
 |
|
Protection Spike |
320 Joules, 2ms |
 |
|
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
|
Protection Overload |
UPS automatic shutdown if overload exceeds
110% of the nominal at 60 sec or exceeds 130% of the nominal
voltage fort 3 seconds |
 |
|
Protection Unit |
Fuse for overload & short circuit
protection |
 |
|
Protection 10 BaseT |
Network (UTP, RJ-45) compatible jacks |
 |
|
Protection Short Protection |
UPS output cut off immediately or
input fuse protection |
 |
|
BATTERY
|
 |
|
Battery Type |
Sealed, Maintenance-free lead acid |
 |
|
Battery Typical |
8 hours (to 90% of full capacity) |
 |
|
Battery Protection |
Automatic self-test & discharge
protection, replace battery indicator |
 |
|
Battery Run Time |
50 - 60 minutes |
 |
|
PHYSICAL
|
 |
|
Physical Weight kgs RM |
10.5 |
 |
|
Physical Weight lbs RM |
(23.1lb) |
 |
|
Physical Shipping Weight kgs |
11.7 |
 |
|
Physical Shipping Weight lbs |
(25.7lb) |
 |
|
Physical Dimension mm Tower |
N/A |
 |
|
Physical Dimension inch Tower |
N/A |
 |
|
Physical Dimension mm RM |
483x362x44 (1U) |
 |
|
Physical Dimension inch RM |
N/A |
 |
|
INDICATOR
|
 |
| LED |
LED |
 |
|
ALARM
|
 |
| Alarm
Battery Backup |
Slow beeping sound (about 0.47 Hz) |
 |
| Alarm
Battery Low |
Rapid beeping sound (about 1.82Hz) |
 |
| Alarm
Overload |
Continue beeping sound |
 |
|
INTERFACE
|
 |
|
Interface RS-232 |
RS-232C Bi-directional communication
port |
 |
|
ENVIRONMENT
|
 |
|
Environment Ambient |
3,500 meters max. elevation, 0-95%
humidity non-condensing, 0-40
°
Celsius |
 |
|
Environment Audible |
<40dBA (1 meter from surface) |
 |
|
Environment Storage Condition |
15,000 meters max. |
|