SLR
-2200P
 
 
 
 
GENERAL INFORMATION
 
Model Name SLR-2200P

 

AC INPUT
 
AC Input Capacity on Battery 2200VA
AC Input Voltage 100 - 120V (+/-) 25% at line input
AC Input Frequency 50/ 60 Hz+/-10% (auto sensing)

 

AC OUTPUT
 
AC Output Voltage Simulated sine ware at 100V/110V/115V/120V/220V/230V/240V +/-5%
AC Output Frequency 50 or 60 Hz +/- 0.5%
AC Output Voltage Regulation AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal
AC Output Transfer 2/4 milliseconds, including detection time

 

PROTECTION
 
Protection Spike 320 Joules, 2ms
Protection EMI/RFI 10dB at 0.15 MHz, 50 dB at 30 MHz
Protection Overload UPS automatic shutdown if overload exceeds 110% of the nominal at 60 sec or exceeds 130% of the nominal voltage fort 3 seconds
Protection Unit Fuse for overload & short circuit protection
Protection 10 BaseT Network (UTP, RJ-45) compatible jacks
Protection Short Protection UPS output cut off immediately or input fuse protection

 

BATTERY
 
Battery Type Sealed, Maintenance-free lead acid
Battery Typical 8 hours (to 90% of full capacity)
Battery Protection Automatic self-test & discharge protection, replace battery indicator
Battery Run Time 85 - 95 minutes

 

PHYSICAL
 
Physical Weight kgs RM 28
Physical Weight lbs RM (61.1lb)
Physical Shipping Weight kgs 30.7
Physical Shipping Weight lbs (67.5lb)
Physical Dimension mm Tower N/A
Physical Dimension inch Tower N/A
Physical Dimension mm RM 483x351x130 (3U)
Physical Dimension inch RM N/A

 

INDICATOR
 
LED LED

 

ALARM
 
Alarm Battery Backup Slow beeping sound (about 0.47 Hz)
Alarm Battery Low Rapid beeping sound (about 1.82Hz)
Alarm Overload Continue beeping sound

 

INTERFACE
 
Interface RS-232 RS-232C Bi-directional communication port

 

ENVIRONMENT
 
Environment Ambient 3,500 meters max. elevation, 0-95% humidity non-condensing, 0~48°C
Environment Audible <40dBA (1 meter from surface)
Environment Storage Condition 15,000 meters max.