GENERAL INFORMATION
|
 |
|
Model
Name |
SLR-3000P |
 |
 |
|
AC INPUT
|
 |
| AC
Input Capacity on Battery |
3000VA |
 |
| Input
Connector |
NEMA
L5-30P
|
| AC
Input Voltage |
100V - 120V
(+/-) 25% at line input |
 |
| AC
Input Frequency |
50/60 Hz +/- 10% (auto
sensing) |
 |
|
AC OUTPUT
|
 |
| AC
Output Voltage |
Simulated sine wave at 100V, 110V,
115V, 120V, 220V, 230V, 240V |
 |
| AC
Output Frequency |
50/60 Hz +/-0.5% |
 |
| AC
Output Voltage Regulation |
AVR automatically increase output
voltage 15% above input voltage |
 |
| AC
Output Transfer |
2/4 milliseconds, including
detection time |
 |
|
PROTECTION
|
 |
|
Protection Spike |
320 Joules, 2ms |
 |
|
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
 |
|
Protection Overload |
UPS automatic shutdown if overload
exceeds 110% nominal voltage for 60 seconds or exceeds
130% of the nominal voltage for 3 seconds |
 |
|
Protection Unit |
Circuit breaker for overload & short circuit
protection |
 |
|
Protection 10 BaseT |
Network (UTP, RJ-45) compatible
jacks |
 |
|
Protection Short Protection |
UPS output cut off immediately or
input breaker protection |
 |
|
BATTERY
|
 |
|
Battery Type |
Sealed, maintenance-free lead acid
batteries |
 |
|
Battery Typical |
8 hours (to 90% of full capacity) |
 |
|
Battery Protection |
Automatic self-test & discharge
protection, replace battery indicator |
 |
|
Battery Run Time |
95-105 minutes |
 |
|
PHYSICAL
|
 |
|
Physical Weight kgs RM |
32.7 |
 |
|
Physical Weight lbs RM |
71.9 |
 |
|
Physical Shipping Weight kgs |
36.3 |
 |
|
Physical Shipping Weight lbs |
79.8 |
 |
|
Physical Dimension mm RM |
483x485.5x130 (3U) |
 |
|
INDICATOR
|
 |
|
LED |
LED |
 |
|
ALARM
|
 |
|
Alarm Battery Backup |
Slow beeping sound (about 0.2 Hz) |
 |
|
Alarm Battery Low |
Rapid beeping sound (about 1 Hz) |
 |
|
Alarm Overload |
Continue beeping sound |
 |
|
INTERFACE
|
 |
|
Interface RS-232 |
RS-232C Bi-directional
communication port |
 |
|
ENVIRONMENT
|
 |
|
Environment Ambient |
3500 meters max. elevation, 0-95%
humidity non-condensing, 0-40°
C |
 |
|
Environment Audible |
<40dBA (1 meter from surface) |
 |
|
Environment Storage Condition |
15,000 meters max. elevation |
|